Página 142 - abchance

Versión de HTML Básico

Jumpers & Load Pi ckup Tool s – 2300
Page 2306
September 2012
Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com
Features & Applications
• Center support for easy application
• Available in four jumper-cable sizes
• Features mid-span orange 8’-long epoxy-resin, fiberglass-
reinforced-plastic (FRP) tube
• Rigid 1-1/2”-O.D. tube serves as a support for easy handling
of jumper set by rubber gloves or hot-line tools
• This makes the unit especially handy when jumpering
switchgear, reclosers or cutting in double deadends
• Completely pre-assembled
• Two non-metallic hangers – one at each end of the FRP
support tube 
• These hangers provide for parking the by-pass clamps while
moving the jumper set into or out of the work area since
the 16’-long jumper cable (with EPR jacket) is secured where
it exits the FRP tube, 4’ of cable extend from both ends of
the rigid support
• Threaded compression assemblies  –  each comprising a
connector, nut and lockwasher, all of copper  –   are applied
at the cable ends
• Two clamps (each a Chance C6001743) also come installed
with cable strain-relief clamps to complete the by-pass
jumper set
Insulated Jumper Sets
Each: 16-ft. overall length (includes 8-ft. tube)
with two C6001743 clamps applied on cable
by copper connector assemblies
Ordering Information
Continuous Current
Rating
200 amperes
260 amperes
300 amperes
400 amperes
Weight
(lb./kg.)
27/12.15
29/13.05
32/14.4
37/16.65
Cable Size,
AWG
#2 – 15kV
1/0 – 15kV
2/0 – 15kV
4/0 – 15kV
Catalog
Number
 ­­C6010260
 ­­C6010261
 C6010262
 C6010263
Insulated By-Pass Jumpers
• Rated for 15 kV phase-to-phase systems
•  Aluminum body with smooth jaws
•  Bronze eyescrew with fine threads
Clamp Specifications
Recommended Torque
250 inch-pounds
Main Line Range:
Minimum
Maximum
#6 Solid Copper (0.162")
1590 kcmil ACSR (1.5")
Terminal threads
5
/
8
"-11 UNC
(plus cable strain-relief
clamps)