Página 169 - abchance

Versión de HTML Básico

Cover -Up Equipment – 2400
Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com
Page 2405
November 2012
Covers
for Conductor, Insulators and Deadends
• 36.6 kV Phase-to-Phase • ASTM Class 4
• Tested to ASTM F712
Conductor cover is 5 feet long and includes an adapter
for handling by Grip-All clampsticks.
Maximum conductor size: 666 kcmil ACSR.
Catalog No.
  C4060514GA
Weight
5
1
/
4
lb./2.36 kg.
Description
5 ft. Conductor Cover
Insulator covers fit 6
1
/
2
" to 9"-diameter pin or post
insulators. Each cover includes an adapter for handling
by Grip-All clampsticks.
C4060557
  C4060557L
3 lb./1.36 kg.
3
1
/
2
lb./1.6 kg.
12" Insulator Cover
16
1
/
2
" Insulator Cover
Deadend cover fits three 10"-diameter porcelain bells or
polymer deadend insulators and includes an adapter for
handling by Grip-All clampsticks.
C4060537
5
1
/
4
lb./2.36 kg.
Deadend Cover
Deadend Cover
C4060537
Insulator Covers
C4060557 (12" height)
and
C4060557L (16
1
2
" height)
Covers on
Crossarm Construction
Covers on Horizontal
Post Construction
Insulator
Cover
couples
with
Conductor
Cover
using Hot
Sticks or
Rubber
Gloves
Conductor Cover
C4060514GA
Deadend Cover couples with Conductor Cover
To meet the Class 4 rating, the deadend cover must be used
in conjunction with a rubber insulating blanket covering the
coupler to the line cover. Failure to use a blanket to cover the
coupler may result in electrical shock, severe injury or death
by electrocution.
• Tested to ASTM F712
• Meet Class 4 requirements
• A versatile system of covering up a variety of
configurations on distribution systems
• Conductor and insulator units mate together to cover
pin-type or post-type insulator construction
• Units virtually surround hot parts and hardware to give
linemen extra protection when rubber gloving or using
hot sticks
• Each item is fitted with an adapter for multi-position
handling by Grip-All clampsticks
• These covers also couple with Chance 25 kV covers
(catalog pages 2402 and 2403) and Classes 2, 3 and 4 of
rubber line hose (pages 2410 and 2411)
• Covers also couple with major brands of rubber
insulator hoods
• All covers are high-density, bright orange polyethylene
in uniform wall thickness
• Excellent dielectric/puncture strength and perform well
from -50° to 170°F
• Ultra-violet stabilizers in material help inhibit
degradation as a result of atmospheric exposure
• Conductor cover is 5’ long
• V-shaped cover’s bottom edge makes it easy to install
• Four indented ribs along cover’s top edge for air gap
between conductor and cover
• Maximum conductor size is 666 kcmil ACSR
• Insulator covers come in two heights: Either 12" or
16-1/2" tall cover fits 6-1/2" to 9"-diameter pin or post
insulators
• Special slits in insulator covers help locate the
conductor and hardware when installing covers
PSC4032879
Grip-All Adapter
Replacement Kit
as furnished on C4060181GA
and C4060514GA Conductor Covers
includes 2 Screws P0010740P and 1 each:
Bracket P4060196P, Adapter E4060211P, Wing
Nut 055067P, Bolt 066713P.
• Deadend cover fits three 10"-dia. porcelain bells or
polymer deadend insulators and couples with line
cover
• To meet the Class 4 rating, deadend cover must be
used in conjunction with a rubber insulating blanket
covering the coupler to the line cover
Failure to use a blanket to cover the coupler may result
in electrical shock, severe injury or death by electrocution