Página 306 - abchance

Versión de HTML Básico

Grounding Equipment – 3000
Page 3018
July 2012
Phone: 573-682-5521 Email: hpsliterature@hubbell.com Web: hubbellpowersystems.com
with Pressure-Type Terminals
Features & Applications
• For grounding substation bus when de-energized for
maintenance
• Makes workmen’s job safer and easier
• Large capacity bus clamps are available in mounted
versions
• Reaches any manageable height
• Increases worker’s lifting capabilities
• Plastisol coated, Shepherd Hook Lift Stick, with block
and rope assembly
• Reduces capacity clamps on overhead bus
• Two sizes of mounted clamps are available:
o C6000618 has 6-5⁄8" bus capacity, utilizing a
C6000337 ground clamp mounted on 1-1⁄4" x 9 ft.
Epoxiglas
®
Pole
o C6000619 has 4" bus capacity, utilizing a G3369
ground clamp mounted on 1-1⁄4" x 8'10" Epoxiglas
®
Pole
• Cables, ferrules and small grounding clamps should be
ordered separately
Accessories
C6000617 — Lift Hook Assembly, 1
1
4
" x 8'8" Epoxiglas
®
pole, includes block and rope assembly.
C6000620 — 1
1
4
" x 12' Extension Pole (middle section).
C6000621 — 1
1
4
" x 8' Bottom Pole.
Substation Grounding Sets
• Epoxiglas
®
handle (42" x 1-1⁄4") meets OSHA electrical
requirements
• Gives operator sufficient added reach needed to make
contacts
• Contact hook of 98%-conductive Copper is double-
bolted to handle
• T-handle aluminum grounding clamp with serrated
flat-face jaw ensures proper bonding
• Jaws open to 1-1⁄2" for attachment to grounded
structural angles, flats or rods
• Extra-flexible (1638 strands) Copper grounding cable,
7 ft., with clear jacket fitted with copper terminal at
each end gives high current-carrying capability
C6000619
C6000618
C6000617
C6000620
Extension Pole
T6000891
Electro-Static Precipitator
Grounding Tool Set
Simple Safety Procedures
• Drains off static charges that remain on collector
plates after electrostatic-precipitator pollution-control
equipment is de-energized
• When electrical system of precipitator is de-energized:
o First, secure the tool’s grounding clamp to a known
ground
o Next, use insulated handle to bring the Copper hook
in contact with the precipitator collector plates
o Contact hook hangs from collector plates (with the
grounding clamp still attached to ground) while
service is performed on precipitator
o When maintenance is completed, use insulated
handle to remove contact hook from collector plates
o Finally, remove the ground clamp before re-
energizing the precipitator
C6000621
Bottom Pole
Catalog Number
C6000618
C6000619
ELECTRICAL RATINGS
Continuous Current (AMPS)
400
400
Fault Current - 15 Cycles (AMPS)
43,000
43,000
Fault Current - 30 Cycles (AMPS)
30,000
30,000
MECHANICAL RATINGS
Recommended Torque (in.-lb.)
250
250
Main Line Range - Max.
6
5
8
” Angles
4
1
2
” Angles
Main Line Range - Min.
4
1
2
” Round
Bus
1/0 Str. Copper
(0.368”)
Jumper Range - Max.
4/0 Grd. Cable
w/Plain Plug
4/0 Grd. Cable
w/Plain Plug
Jumper Range - Min.
#2 Grd. Cable
w/Plain Plug
#2 Grd. Cable
w/Plain Plug
Weight Each
10 lb./4.5 kg.
9
1
4
lb./4.2 kg.
ASTM Designation
Type II
Class A
Grade 5
Type II
Class A
Grade 5
Catalog No.
Description
Weight, each
T6000891 Electrostatic Grounding Set
7 lb./3.2 kg.