Página 147 - BURNDY

Versión de HTML Básico

Conductor
Installation Tooling
Stud
Figure
Mechanical
Hydraulic
Wire
*** Hole Tongue
Dimensions
Dieless
MD6, OUR840,
BCT500HS,
Y35, Y39, Y750,
Color Die Strip
Catalog Number
Fig #
AWG
MM
2
Size Width (B)
(T)
(L)
(# of crimps)
MD7-34R Y500CTHS Y46*, PAT750 Code Index Length
YAZV10TC14
1
#14 - 10 Str
6 1/4 .41 .69 .05 1.54 Y8MRB-1
— — — — — 3/4
#12 - 10 Sol
.
YAZ8CTC10
1
#10 .41 .75 .08 1.58
#8 AWG
W8CVT (2) W8CVT (2)
YAZ8CTC14
1
#8 Weld
† 1/4 .44 .75 .08 1.71 Y1MRTC (2) W8CRT (2) W8CRT (2)
U8CRT (2)
Red 49 7/8
37/24
10
MY29-3 (2)
X8CRT (2)
X8CRT (2)
YAZ8CTC38
1
#6 Sol
3/8 .58 .75 .06 1.89 MY29-11 (2)
MRC840 (2) W5CVT (2) W5CVT (2)
YAZ6CTC14
1
1/4 .45 1.12 .08 2.03
Y644HS (1)
W5CRT (2) W5CRT (2)
U5CRT (2)
7 or
YAZ6CTC38
1
#6 AWG —
3/8 .58 1.12 .06 2.22 Y81KFT (1)
X5CRT (2)
X5CRT (2)
U8CABT (2)
Blue
374
1-3/16
YAZ6CTC12
1
1/2 .83 1.12 .12 2.65 Y81KFTMBH (1) X8CART (2) X8CART (2)
.
PAT81KFT-18V (1) W5CRT (2) W5CVT (2)
YAZ5CTC12
1 #5 AWG — 1/2 .83 1.12 .12 2.68
W5CVT (2)
X5CRT (2)
U5CRT (2)
Blue
7 or
1-3/16
X5CRT (2)
W5CRT (2)
374
Y1MRTC (4)
YAZ4CTC14
1
1/4 .49 1.12 .09 2.05 MY29-3 (2)
MY29-11 (2)
MRC840 (2)
W4CVT (2) W4CVT (2)
U4CRT (2)
8 or
YAZ4CTC38
1 #4 AWG — 3/8 .58 1.12 .08 2.23
Y644HS (1)
W4CRT (2) W4CRT (2)
U6CABT (2)
Gray
346
1-3/16
Y81KFT (1)
X4CRT (2)
X4CRT (2)
YAZ4CTC12
1
1/2 .73 1.12 .06 2.50 Y81KFTMBH (1)
PAT81KFT-18V (1)
ONE HOLE HYLUG™
CODE CONDUCTOR
LONG BARREL WITH
INSPECTION WINDOW
TYPE YAZ
UNINSULATED COPPER
COMPRESSION TERMINAL
UL Listed 90° C,
600 Volts to 35 kV
45° and 90° angles are available.
Please contact Customer Service to order:
1-800-346-4175
ELECTRO-TIN
PLATED
CABLE
ACCOMMODATION
CRIMP
DIE AND COLOR
CODE INFORMATION
INSPECTION
WINDOW
BEVELED
ENTRY
T
T
90°
L
L
45°
L
B
T
B
B
Fig. 1
45°
90°
* Use PUADP-1 adapter with U dies in Y46 HYPRESS™.
** P-RT die sets for use in Y46 HYPRESS™ only, PUADP-1
adapter not required.
*** The MM
2
conductor sizes listed are the recommendations
for Class 2 conductor.
† The MM
2
conductor size listed is for Class 2 and Class 5
conductor.
See tooling section of this catalog for complete tool and
die listings.
• Available undrilled. Add suffix U to catalog number
(example: YA25U).
For applications greater than 2000 Volts consult cable
manufacturer for voltage stress relief instructions.
Note:
All dimensions shown are for reference only.
Blue highlighted items are industry standard and most frequently ordered.
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
C-27
BURNDY
®
Compression Connections
Copper Compression — Code — Long Barrel — Inspection Window