Página 150 - BURNDY

Versión de HTML Básico

Conductor
Installation Tooling
Stud Stud
Figure
Mechanical
Hydraulic
Wire
Fig
*** Hole Hole Tongue
Dimensions
Dieless
MD6, OUR840,
BCT500HS,
Y35, Y39, Y750,
Color Die Strip
Catalog Number
#
AWG MM
2
Size Spacing Width (B)
(T)
(L)
(# of crimps)
MD7-34R Y500CTHS Y46*, PAT750 Code Index Length
YAV10-2TC10
1
# 10 5/8 .38 .38 .06 1.72
YAV10-2TC14
1
1/4 5/8 .47 .38 .06 1.84
YAV10-2TC14E1
1
#14-10 Str.
6 1/4 1 .47 .38 .05 2.22 Y8MRB-1 (1)
— — — — — 7/16
YAV10-2TC14E2
1
#12-10 Sol.
1/4 3/4 .47 .38 .05 1.97
YAV10-2TC38
1
3/8 1 .56 .38 .04 2.40
YA8CL-2TC10
1
# 10 5/8 .41 .44 .08 1.83 Y1MRTC (1)
YA8CL-2TC10E2
1
# 10 3/4 .41 .44 .08 1.95 Y8MRB-1 (1)
YA8CL-2TC14
1 #8 AWG
1/4 5/8 .44 .44 .08 1.95 MY29-3 (1)
#8 Weld †
MY29-11 (1)
W8CVT (1) W8CVT (1)
YA8CL-2TC14E1
1
37/24 10
1/4 1 .44 .44 .08 2.33
MRC840 (1)
W8CRT (1) W8CRT (1)
U8CRT (1)
Red 49 1/2
YA8CL-2TC14E2
1 #6 Sol.
1/4 3/4 .44 .44 .08 2.08 Y81KFT (1)
X8CRT (1)
X8CRT (1)
YA8CL-2TC38
1
3/8 1 .57 .44 .06 2.52 Y81KFTMBH (1)
YA8C-2LN
1
1/2 1-3/4 .83 .44 .12 3.75 PAT81KFT-18V (1)
YA6C-2L
1
1/4 5/8 .45 .54 .08 2.01
YA6C-2LN
1
1/2 1-3/4 .81 .54 .12 3.87
YA6CL-2TC10
1
# 10 5/8 .42 .54 .09 1.94
YA6CL-2TC14
1
1/4 5/8 .45 .54 .08 2.07 Y1MRTC (1)
YA6CL-2TC14E
1
1/4 1/2 .45 .54 .08 1.94 MY29-3 (1)
YA6CL-2TC14E1
1
1/4 1 .45 .54 .08 2.44 MY29-11 (1)
W5CVT (1) W5CVT (1)
YA6CL-2TC14E2
1
6 AWG —
1/4 3/4 .44 .54 .08 2.19 MRC840 (1)
W5CRT (1) W5CRT (1)
U5CRT (1)
Blue 7 5/8
YA6CL-2TC38
1
3/8 1 .63 .54 .06 2.63 Y81KFT (1)
X5CRT (1)
X5CRT (1)
U8CABT (1)
YA6C-2L51
1
# 10 1/2 .42 .54 .09 1.79 Y81KFTMBH (1)
X8CART (1) X8CART (1)
YA6CL-2TC516
1
5/16 1 .52 .54 .07 2.51 PAT81KFT-18V (1)
YA6CL-2TC516E2
1
5/16 3/4 .52 .54 .07 2.26
YA6C-2L52
1
1/4 1/2 .45 .54 .08 1.88
YA5C-2L
1 5 AWG — 1/4 5/8 .44 .81 .07 2.28
7/8
TWO HOLE HYLUG™
CODE CONDUCTOR
STANDARD BARREL
TYPES YAV-2TC, YA-L2L,
YA-2LN, AND YA-L-2TC
COPPER COMPRESSION
TERMINAL
UL Listed 90° C,
600 Volts to 35 kV
45° and 90° angles are available.
Please contact Customer Service to order:
1-800-346-4175
-- Color code not assigned.
* Use PUADP-1 adapter with U dies in Y46 HYPRESS™.
** P-RT die sets for use in Y46 HYPRESS™ only, PUADP-1
adapter not required.
ELECTRO-TIN
PLATED
CABLE
ACCOMMODATION
CRIMP
DIE AND COLOR
CODE INFORMATION
INSPECTION
WINDOW
BEVELED
ENTRY
T
T
T
B
B
B
Fig. 1
45°
90°
*** The MM
2
conductor sizes listed are the recommendations
for Class 2 conductor.
† The MM
2
conductor size referenced here is for both Class
2 and Class 5.
See tooling section of this catalog for complete tool and
die listings.
For applications greater than 2000 volts consult cable
manufacturer for voltage stress relief instructions.
Note:
All dimensions shown are for reference only.
Blue highlighted items are industry standard and most frequently ordered.
Canada: 1-800-387-6487
www.burndy.com
US: 1-800-346-4175
C-30
Compression Connections
BURNDY
®
Copper Compression — Code — Inspection Window