TYPES Y-R
REDUCING ADAPTER
FOR COPPER
600 Volts to 35 kV
The Y-R reducing adapter has been designed
to allow large size, long barrel, copper long
barrel HYDENT™, HYSPLICE™ and
HYTEE™ terminals, splices, and T taps to be
used on smaller conductor sizes. To use,
simply insert the reducer into the barrel,
insert the wire into the reducer adapter and
crimp the outer barrel using its recommend-
ed tooling.
Crimp with U34RT, 4 crimps each side (a total of 8 crimps).
Features and Benefits
• Wide range of conductors are
accommodated.
Lowers inventory requirements and
affords maximum versatility.
• Same die set for all legs of the connection.
Permits the same tool and die
combination normally used on
the compression barrel.
• Length fits the long barrel connector
design (YS, YA).
Can be used on all long barrel
connectors. Field cut to fit shorter
length compression barrels (YS-L, YA-L).
• Manufactured from high conductivity
electrolytic copper and electro-tin plated.
Provides maximum conductivity low
resistance and ductility for an excellent
combination of electrical and crimp
forming properties, and provides
long lasting corrosion resistance.
Y3428R
APPLICATION EXAMPLE
ELECTRO-TIN
PLATED
INTERNALLY
BEVELED ENDS
WIRE RANGE
Insert reducing adapter into splice connection as shown.
Catalog
Wire Range
Dimensions
Number
From
To
Max O.D.
L
Y286CR
6, 8 str. 6 sol.
Y284WR
4 sol.
Y284CR
4 str.
Y282CR
2 str.
Y281CR
4/0 str.
1 str.
.534 1.75
Y2825R
1/0 str.
Y2826R
2/0 str.
Y2827R
3/0 str.
Y2928R
250 kcmil
4/0
.582 1.62
Y302CR
2
Y304CR
4
Y3025R
1/0
Y3026R
300 kcmil
2/0
.637 2.00
Y3027R
3/0
Y3028R
4/0
Y3126R
2/0
Y3128R
350 kcmil
4/0
.687 2.00
Y3129R
250
Y342CR
2 str.
Y3425R
1/0 str.
Y3426R
2/0 str.
Y3427R
3/0 str.
Y3428R
500 kcmil
4/0 str.
.821 2.50
Y3429R
250 kcmil
Y3430R
300 kcmil
Y3431R
350 kcmil
Y3432R
400 kcmil
Y3934R
500 kcmil
Y3936R
750 kcmil
600 kcmil
1.017 2.25
Y4439R
1000 kcmil
750 kcmil
1.296 3.19
YS34
Contact Technical Support for other sizes not listed.
For applications greater than 2000 Volts consult cable
manufacturer for voltage stress relief instuctions.
Note:
All dimensions shown are for reference only.
Blue highlighted items are industry standard and most frequently ordered.
Canada: 1-800-387-6487
www.burndy.com
US: 1-800-346-4175
C-84
Compression Connections
BURNDY
®
Copper Compression — Code — Reducing Adapter