Página 235 - BURNDY

Versión de HTML Básico

TYPES YA-A
AND YA-A-TN
(Continued)
HYLUG™
UNINSULATED ALUMINUM
COMPRESSION TERMINAL
FOR ALUMINUM AND
COPPER CONDUCTORS
1-HOLE DESIGN
AL9CU
• Contact BURNDY
®
for conductor, stud sizes and hole
drillings not shown.
See tooling section of this catalog for complete tool and
die listings.
Y644HS DIELESS HYPRESS™
RANGE-TAKING
CAPABILITIES
The following size HYDENT™ lugs and two
way splices, when crimped with the Y644HS
DIELESS HYPRESS™ tool, produce the
following range taking capabilities:
DIE AND CRIMP
INFORMATION
ELECTRO-TIN
PLATED
CLOSED
BARREL
COLOR CODED
END CAP
CRIMP
CRIMP
CABLE
ACCOMMODATION
Aluminum Connectors
Standard
Expanded Standard Expanded Standard
Expanded
Wire Size
Wire Range Wire Size
Wire Range
Wire Size
Wire Range
#6 AWG
#6 AWG
1/0 AWG 1/0 - #1 AWG 250 kcmil
250 kcmil - 1/0 AWG
#4 AWG
#4 - #6 AWG 2/0 AWG 2/0 - #1 AWG 300 kcmil
300 kcmil - 2.0 AWG
#2 AWG
#2 - #6 AWG 3/0 AWG 3/0 - #1 AWG 350 kcmil
350 kcmil - 3/0 AWG
#1 AWG
#1 - #2 AWG 4/0 AWG 4/0 - #1 AWG 400 kcmil
400 kcmil - 4/0 AWG
500 kcmil
500 kcmil - 4/0 AWG
600 kcmil
600 - 250 kcmil
750 kcmil
750 - 500 kcmil
* Use PUADP-1 adaptor with U dies in Y46 Hypress™.
** P44ART for use with Y46 HYPRESS™ only. PUADP-1
adapter not required.
+ Tested with Y644HS and PAT644 dieless tools only and
Dimensions
Installation Tooling
Dieless (# of crimps)
Y35, Y39, Y750, Y46*
Wire
Catalog
Code
Stud
No. of
T Z Mechanical
Hydraulic Die Number
Color
Die
Strip
Number
Conductor
Size Holes in Pad C D L N REF. Min.
Tooling HYPRESS™ (# of crimps)
Code Index Length
YA4CA1
1/4
.47 .75 2.13 .33 .18 .42
Y81KFT (1)
YA4CA3
5/16
.80 .87 2.25 .41 .12 .46 MY29-3 (1) Y81KFTMBH (1)
4 str.
1
MRC840AL (1) PAT81KFT-18V (1)
U4CABT (1)
Green 375 7/8
YA4CA6
3/8
.80 .94 2.32 .44 .12 .50
Y644HS (1)
YA2CA5
1/4
.50 .91 2.25 .32 .22 .43
YA2CA1
2 str.
5/16
1
.88 1.03 2.50 .41 .16 .47
U2CABT (1)
Pink
348 1-1/8
YA2CA3
3/8
.88 1.03 2.56 .44 .16 .50
YA1CA1
1 str.
3/8
1
.76 1.19 2.59 .44 .19 .75
MY29-3 (1)
U1CART (1)
Gold 471 15/16
YA25A1
5/16
.60 .87 2.31 .41 .21 .46
MRC840AL (1)
YA25A3
1/0 str.
3/8
1
.82 1.18 2.67 .63 .21 .55
U25ART (1)
Tan
296 1-1/16
YA25A9
1/2
1.03 1.34 2.67 .63 .17 .71
Y81KFT (2)
YA26A6
3/8
.67 1.18 2.79 .44 .24 .74
Y81KFTMBH (2)
YA26A1
2/0 str.
1/2
1
1.03 1.36 3.03 .63 .20 .73
Y644HS (1)
U26ART (2)
Olive 297 1-3/8
YA27A1
3/8
.73 1.18 2.88 .44 .26 .74 MY29-3 (2) PAT81KFT-18V (2)
YA27A3
3/0 str.
1/2
1
1.04 1.37 3.27 .63 .26 .74 MRC840AL (2)
U27ART (2)
Ruby
467 1-1/2
YA28A1
3/8
1.17 1.18 3.26 .44 .30 .74
YA28A3
4/0 str.
1/2
1
1.17 1.36 3.44 .63 .30 .73
U28ART (2)
White 298 1-5/8
YA29A1
250 kcmil
1/2
1
1.26 1.36 3.53 .63 .33 .73
U29ART (2)
Red
324 1-5/8
YA30A6
3/8
1.38 1.37 3.90 .63 .36 .74
YA30A1
300 kcmil
1/2
1
1.38 1.37 3.90 .63 .36 .74
U30ART (2)
Blue 470 1-3/4
Y644HS (1)
Y81KFT (3)
YA31A1
350 kcmil
1/2
1
1.52 1.37 4.33 .63 .39 .74
Y81KFTMBH (3)
U31ART (2)
Brown 299 2-1/8
PAT81KFT-18V (3)
YA32A1
400 kcmil
5/8
1
1.62 1.88 4.92 .88 .43 1.00
U32ART (4)
Green 472 2-1/2
YA34A1
500 kcmil
5/8
1
1.80 1.91 5.56 .88 .46 1.03
Y644HS (1)
U34ART (4)
Pink
300 2-5/8
YA36A1
600 kcmil
5/8
1
1.97 1.88 5.82 .88 .52 1.00
Y81KFT (4)
U36ART (4)
Black 473 2-7/8
YA39A1
700/750 kcmil
1/2
2.05 1.34 5.26 .63 .43 .71
Y81KFTMBH (4)
YA39A3
900 Compact AL + 5/8
1
2.05 1.88 5.80 .88 .43 1.00
PAT81KFT-18V (4)
U39ART-2 (4)
Yellow 936 2-7/8
YA44A1
1000 kcmil
5/8
1
2.50 1.89 6.50 .88 .43 1.01
P44ART** (4)
Brown 302
3
not UL Listed with any tool on 900 Compact Al.
For applications greater than 2000 Volts consult cable
manufacturer for voltage stress relief instructions.
Note:
All dimensions shown are for reference only.
UL Listed 90° C,
600 Volts to 35 kV
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
C-115
BURNDY
®
Compression Connections
Aluminum Compression — Tin Plated — For Aluminum & Copper Conductors