Página 262 - BURNDY

Versión de HTML Básico

BURNDY
®
Grounding
HYGROUND
®
Compression
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
Blue highlighted items are industry standard and most frequently ordered.
E-9
TYPE YGHP-C
HYTAP™ CONNECTOR
Irreversible compression ground tap figure 6
can be used as a tap connector or as a tap
splice connector. Four die sets and eight con-
nectors can accommodate a conductor
range from #8 solid through 500 kcmil plus
1/2 , 5/8 , and 3/4 copper bonded ground
rods. UL467 Listed. Acceptable for direct
burial in earth and concrete. Prefilled with
PENETROX™ compound and strip sealed.
NOTES:
When using #6 Sol. in tap, fold conductor double to
improve fill in YGHP2C2.
For YGHP29C29 when using 3/0 in tap, minimum run
conductor is 2/0 Str.
Where a 'U' or 'PU' die is recommended with the Y45
HYPRESS™, a PT6515 adapter must be used.
Where a 'U' or 'PU' die is recommended with the Y45
HYPRESS™, a P-UADP-1 adapter must be used.
For increased rotational resistance on ground rods,
pre-crimp ground rod with U2CABT die Index 348
or uprecrimp dies may be used for even greater
rotation and vibration resistance on ground rods.
CABLE TO GROUND ROD
CABLE TO REBAR
CABLE TO CABLE
FOR CONCRETE ENCASED
ELECTRODE GROUNDING
APPLICATIONS
Fig. 1
Fig. 2
UL96 Listed for Lightning Protection.
Installation Data
Die Y750/Y35
➂ ➃
Catalog
Fig.
Accommodates
Cable To Rebar
Index
Y39
Y45
Y46
No. of
Number
No.
Run
Tap
Run
Tap
B No.
HYPRESS™ PAT750-18V HYPRESS™ HYPRESS™ Crimps
YGHP2C2
1
#6 Sol. (0.162) {59500} –
#6 Sol. (0.162) {#2 Str.} –
#2 Str. (0.292) {59500}
#2 Str. (0.292) {#2 Str.}
0
U0
U0
U0
U0
1
YGHP2C6W6W
2
#6 Sol. (0.162) –
#8 Sol. (0.128) –
#2 Str. (0.292)
6 Str. (0.184) Qty. 2
YGHP29C6W6W
2
#8 Sol. (0.128) –
#8 Sol. – 6 Str.
6 Str. (0.184) Qtr. 2
#3 Rebar
YGHP29C2
1 1/0 Str. (0.372) {98500} –
#4 Sol. (0.204) {#4 Sol.} –
3/8
#2 Str.
250 kcmil (0.575) {131500}
#2 Str. (0.292) {#2 Str.}
997
U997
U997P
U997
U997
1
YGHP29C26
1
1/2 – 5/8 Rod
1/0 Str. (0.372) {98500} –
thr0ugh
1/0 Str. – 2/0 Str.
.75
2/0 Str. (0.419) {98500}
1/2
[19]
YGHP29C29
1
3/0 Str. (0.470) {131500} – #4 Rebar
3/0 Str. – 250 kcmil
250 kcmil (0.575) {211500}
YGHP34C2
1
#4 Sol. (0.204) –
#5 Rebar
#2 Str. (0.292)
5/8
YGHP34C26
1
250 kcmil (0.575) {250 kcmil} –
1/0 Str. (0.372) {98500} –
1/0 Str. – 2/0 Str.
998 PU998
PU998
PU998 or
PU998 or
1
500 kcmil (0.813) {500 kcmil}
2/0 Str. (0.419) {98500}
S998
P998
YGHP34C29
1
5/8 – 3/4 Rod
3/0 Str. (0.470) {131500} –
through
3/0 Str. – 250 kcmil
250 kcmil (0.575) {211500}
250 kcmil (0.575) –
350 kcmil (0.681) –
3/4
1.10
YGHP34C34
1
500 kcmil (0.813)
#6 Rebar 350 kcmil – 500 kcmil
1011
U1011
U1011
S1011
P1011
3
5/8 – 3/4 Rod
500 kcmil (0.843)
[28]
Dimensions in brackets { } represent lightning protection
conductors.
467 96
Clean rust and protective coatings from rebar before con-
nector installation to provide a proper ground connection.
Precrimping is not required.
These connectors can only be installed using the Y750,
Y45 or Y46 HYPRESS™ with the recommended dies.
These connectors can not be installed with the Y35 and
Y39 HYPRESS™.
Polarized die for the PAT750-18V.
Not UL96/CSA.
Ground Rod
Dia.
PRECRIMP Dies
1/2
UPRECRIMP 12
5/8
UPRECRIMP 58 U2CABT
3/4
UPRECRIMP 34
IEEE-837