Grounding
HYGROUND
®
Compression
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
Blue highlighted items are industry standard and most frequently ordered.
E-15
TYPE YGHR-C
HYTAIL™
High Strength Irreversible
Compression Ground Rod
Tap Connectors
Type YGHR-C irreversible compression
grounding connector is engineered specifical-
ly for the Telecommunications Industry for
(1, 2 or 3) #2 solid, tinned or bare conductor
taps. UL467 Listed. Acceptable for direct bur-
ial in earth or concrete. BURNDY
®
has
designed this connector to meet the stringent
requirements of OSHA, the National Electric
Code (NEC), UL, and the Telecommunications
Industry. Performance and long life are this
connector’s basic design guidelines.
Features and Benefits
• Tap side 1, 2 or 3 conductors.
One connector style can be used for
many applications.
• Material is high conductivity wrought
copper extrusion, identical material to
the conductor.
High-conductivity copper minimizes
resistance and voltage drop. Eliminates
the possibility of corrosion due to
dissimilar metals.
• System engineered tooling.
Each tooling recommendation has
been designed to provide a reliable,
dependable connection.
• Contact BURNDY
®
for other ground rod diameters.
* PU998 and U1011 die sets require PUADP-1 adapter for
use in the Y46 HYPRESS™.
Tap positions may be left void when fewer than (3) con-
ductors are used.
+ To order electro-tin plated connector for use on galvanized
steel ground rod add suffix -”TN” to the catalog number.
NOTE:
The ground rod hole diameter is larger for galvanized
steel ground rod in the tin plated connector.
TAP
TAP
RUN
RUN
AND
• The die index number is embossed on
connector after completion of crimp.
Facilitates speedy inspection of installed
connectors to ensure consistently
reliable and dependable connections.
• Prefilled with PENETROX™ and individually
sealed in clear polyethylene sheet.
Ensures the electrical integrity of the
finished connection by inhibiting mois-
ture and contaminates from entering the
contact area. Maintains long-term
high-conductivity.
• UL 467 Listed. Acceptable for direct burial.
May be used in direct burial or concrete
embedded grounding applications.
Provides quality assurance to recog-
nized industry NEC standards from an
independent party.
† Ground rod must be precrimped with die U2CABT (Index
No. 348) when PU998 die set is used in the Y35, Y750 or
Y46.
HYPRESS™ tools. For even greater mechanical resistance
use UPRECRIMP 58 dies.
** The Y750 utilizes PU dies and the U1011 die. The Y35
only uses PU998 die set.
NOTE:
A 12 bend radius is recommended for the conductor.
Installation Tooling
PAT750/Y35/Y750**
Y46*
Catalog
Ground Rod
Die
No. of
Die
No. of
Die
Number +
Diameter •
Tap Conductor
No.
Crimps
No.
Crimps
Index
PU998†
(1)
#2 Sol. Copper 1, 2, or 3
PU998†
(1)
U1011
(2)
998 or
YGHR58C2W-3
5/8
may be connected
P998
(1)
1011
U1011
(2)
P1011
(2)