Página 269 - BURNDY

Versión de HTML Básico

Grounding
BURNDY
®
HYGROUND
®
Compression
Canada: 1-800-387-6487
www.burndy.com
US: 1-800-346-4175
Blue highlighted items are industry standard and most frequently ordered.
E-16
TYPE YGHA
HYLUG™
Heavy Duty Irreversible
Compression Terminals
Heavy duty HYLUG™ irreversible compres-
sion terminals designed not only to carry
short circuit load, but to also withstand high
mechanical stress. Each conductor element
has an inspection probe hole to ensure
proper cable insertion. UL467 Listed.
Acceptable for direct burial in earth or con-
crete. UL486A Listed. Prefilled with PENE-
TROX™ compound and strip sealed.
TYPE YGHS
HYLINK™
Heavy Duty Irreversible
Compression Terminals
Heavy duty HYLINK™ ground splice
designed not only to carry short circuit load,
but to also withstand high mechanical stress.
Each conductor element has an inspection
probe hole and a center stop to ensure
proper cable insertion. UL467 Listed.
Acceptable for direct burial in earth or
concrete. UL486A Listed. Prefilled with
PENETROX™ compound and strip sealed.
Where a “U” or “PU” die is recommended with the Y45
HYPRESS™, a PT6515 adapter must be used.
Where a “U” or “PU” die is recommended with the Y45
HYPRESS™, a PT6515 adapter must be used.
INSPECTION PROBE HOLES
FOR CABLE STOP
KNURLED
RINGS
IEEE-837
IEEE-837
Installation Tools, Die Set Catalog Number,
Catalog
and (Number of Crimps)
Number
Copper Conductor Size
HYPRESS™ Y35/Y39/Y45
/Y46
/Y750 /PAT750
B
C
L
T
YGHA2C-2N
2 str.
U1CRT (1)
.75
.97 4.21 .26
YGHA25-2N
1/0 str.
U27RT (1)
.83
.91 4.60 .19
YGHA26-2N
2/0 str.
U28RT (1)
.83
.97 4.38 .26
YGHA27-2N
3/0 str.
U29RT (1)
1.18 1.08 4.94 .29
YGHA28-2N
4/0 str.
U30RT (2)
1.18 1.22 4.94 .30
YGHA29-2N
250 kcmil
U31RT (2)
1.18 1.28 4.94 .34
YGHA31-2N
350 kcmil
U34RT (2)
1.18 1.62 5.00 .43
YGHA34-2N
500 kcmil
U36RT (3)
1.48 1.72 5.42 .40
Installation Tools, Die Set Catalog Number,
Catalog
and (Number of Crimps)
Number
Copper Conductor Size
HYPRESS™ Y35/Y39/Y45
/Y46
/Y750 /PAT750
B
L
YGHS2C
2 str.
U1CRT (1)
.75
1.73
YGHS25
1/0 str.
U27RT (1)
.83
1.89
YGHS26
2/0 str.
U28RT (1)
.83
1.89
YGHS27
3/0 str.
U29RT (1)
1.18
2.59
YGHS28
4/0 str.
U30RT (2)
1.18
2.59
YGHS29
250 kcmil
U31RT (2)
1.18
2.59
YGHS31
350 kcmil
U34RT (2)
1.18
2.59
YGHS34
500 kcmil
U36RT (3)
1.48
3.19
Where a “U” or “PU” die is recommended with the Y46
HYPRESS™, a PUADP-1 adapter must be used.
Where a “U” or “PU” die is recommended with the Y46
HYPRESS™, a PUADP-1 adapter must be used.