Grounding
HYGROUND
®
Compression
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
Blue highlighted items are industry standard and most frequently ordered.
E-19
TYPE YGF
GROUNDING PLATE
The irreversible compression ground plate is
designed to withstand the rigors of concrete
construction. The ground plates are made of
high strength, high-conductivity cast copper
alloy body with a pure wrought copper
compression element. In addition to the
tapped NEMA size holes and spacing on the
face, the plate comes with a tapped hole on
the underside for ease of positioning prior to
pouring the concrete. UL467 Listed.
Acceptable for direct burial in earth or
concrete. Prefilled with PENETROX™
compound and strip sealed.
NOTES:
This tapped hole may be used to position the grounding
plate on a threaded rod prior to placement of the concrete.
ORDERING INFORMATION
Where a “U” or “PU” die is recommended
with the Y45 HYPRESS™, a PT6515
adapter must be used.
Fig. 1
Fig. 2
IEEE-837
3/8-16 thread with 1.00 EFF. Thread is standard. If other
thread is required, add appropriate Code No. to Catalog
No. for desired thread.
-50 (1/2 -13, .94 EFF. Thread), -62 (5/8 -11, .94 EFF.
Thread) and -75 (3/4 -10, .81 EFF. Thread)
Example: YGF34-4N-50 is YGF34-4N with 1/2 -13 Thread
Plastic plugs are provided to keep dirt out of the threaded
holes until the attachment of grounding terminals.
Catalog
Number
Fig. No.
C
D
H
L
T
Y
YGF29-2N
1
2.00
3.25
3.62
5.78
1.31
2.00
YGF29-4N
2
3.25
3.25
3.62
5.78
1.31
2.00
YGF34-2N
1
2.00
3.25
4.62
5.40
1.31
2.19
YGF34-4N
2
3.75
3.75
4.62
5.90
1.31
2.19
Installation Tools,
Die Set Cat. No., and
(number of crimps)
Catalog
Copper
Tapped Holes
HYPRESS™
Number
Conductor Range
Size
Hole Centers
PAT750/Y750/Y35/Y39
Y45
Y46
YGF29-2N
2 - 250 kcmil
1/2 - 13
1-3/4
U997 (1)
U997 (1)
U997 (1)
YGF29-4N
2 - 250 kcmil
1/2 - 13
1-3/4
U997 (1)
U997 (1)
U997 (1)
YGF34-2N*
250 - 500 kcmil
1/2 - 13
1-3/4
U1011 (3)
S1011 (2)
P1011 (2)
YGF34-4N
*
250 - 500 kcmil
1/2 - 13
1-3/4
U1011 (3)
S1011 (2)
P1011 (2)
Where a “U” or “PU” die is recommended
with the Y46 HYPRESS™, a PUADP-1
adapter must be used.
* These connectors can only be installed
using the Y750, Y45 or Y46 HYPRESS™
with recommended dies. These connec-
tors CAN NOT be installed with the Y35 or