Grounding
HYGROUND
®
Compression
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
Blue highlighted items are industry standard and most frequently ordered.
E-23
TYPES YGT & YTTAG
STATIC GROUNDING
RECEPTACLE
Type YGT static grounding receptacles are
designed for static grounding of equipment.
The receptacle is connected to the ground
grid with HYGROUND
®
compression
connectors and finished flush with surface to
provide a permanent corrosion proof
grounding point.
* When using U or PU dies with Y46 HYPRESS™, a PUADP-1
adapter is required.
NOTES:
1. Ground rod must be pre-crimped with U2CABT die set
when PU998 die is used or for even higher mechanical
resistance use special UPRECRIMP dies on ground rods.
2. Pre-crimping of ground is not necessary when P1011 die
is used. Install YGHR or YGLR on hub Y. Hub Z is inserted
into 1/2” rigid conduit. The conduit is driven into earth to
provide support and provide correct level of receptacle
prior to cement pour.
Type YTTAG Combination
Static Grounding Receptacle
and Aircraft Tie Down Bar
Type YGT Static
Grounding Receptacle
with Cover
Fig. 1
Fig. 2
Catalog
Figure
Dimensions
Number
Number
* HYGROUND
®
Connector
H
D
Y Dia.
Z Dia.
TD
YGT275
1
Select suitable YGHR or
5.5
2.75
.75
.56
YGLR for 3/4 ground rod and
YTTAG388
2
sized to ground conductor.
6.5
4.75
.75
.56
4.3