TYPE BDT
BONDIT™ INTERSYSTEM
BONDING CONNECTOR
House Mounted or
Meter Socket Mounted
Designed to meet the requirements of 2008
NEC Article 250.94 “Bonding for Other
Systems.” Corrosion-resistant stainless steel
set screws. Accepts main ground wire (#2-#8)
and up to 4 intersystem wires (#6-#14). Same
design can be mounted directly to the meter
socket or mounted to the house. Innovative
design does not damage meter socket and
will not void warranty.
Catalog Number:
BDT1
Features & Benefits
• Made in the USA!
• Meets Intersystem Bonding Requirements:
NEC2008 250.94
• One connector does it all
• House mount or meter socket mount
• Incorporates proven BURNDY
®
SERVIT
POST™ design
• Stainless steel set screws
• Accepts main ground wire (#2-#8), up to 4
intersystem wires (#6-#14)
• Easily mounts to meter box during new
installation or can be wall mounted
• Easy to follow instructions included
• Does not damage meter socket; no worries
about damaging the paint or voiding war-
ranties
• Easily installed with a wrench and screw-
driver
• Open design prevents buildup of hornets,
bees, spiders
CONFIGURATION 1 —MOUNTED TO ENCLOSURE
1. Punch out a 1/2 or 3/4 knock out on the electrical enclosure.
2. Begin assembly by installing the ground electrode conductor in
the SERVIT POST™ inside the electrical enclosure. Torque on
SERVIT
®
nut: 275 in-lb max.
3. Install the rest of the connector as shown in figure 1 below, it is not
necessary for the bus bar to be aligned parallel with the enclosure.
(Note: the split washer is not used in this configuration.)
4. Tighten the intersystem ground wires with set screws in the bus
bar to a maximum torque of 35 in-lb.
5. Adhere the BONDIT™ location sticker to the front of the electrical
enclosure.
CONFIGURATION 2 — MOUNTED TO EXTERIOR WALL
1. Begin by assembling the connector as shown in figure 2 below. Be
sure SERVIT POST™ is as tight as it can be while its groove is
aligned with the ground electrode conductor. (Note: the flat wash-
er is not used in this configuration.)
2. Use two mounting screws (not included) to secure the connector
to the exterior wall so that the set screws in the bus bar face
downward.
3. Install the ground electrode conductor into the SERVIT POST™
while turning the nut/pressure bar assembly to a maximum torque
of 275 in-lb. (use 2 wrenches if necessary).
4. Tighten the intersystem ground wires with the set screws in the
bus bar to a maximum torque of 35 in-lb.
5. If hidden from view, use the BONDIT™ location sticker to indicate
the location.
Flat
washer
Plastic
disk
Set screw
Bus bar
SERVIT
POST™
Electrical
enclosure
(cut away)
BONDIT™
locaton
sticker
Ground
electrode
conductor
Intersystem
ground wire
Split lock-
washer
Nut & Pressure
Bar Assembly
SERVIT
POST™
Set screw
Exterior
wall
Mounting
screws (not
included)
Intersystem
ground wire
Ground electrode
conductor