Página 304 - BURNDY

Versión de HTML Básico

BURNDY
®
Grounding
Mechanical
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
Blue highlighted items are industry standard and most frequently ordered.
E-51
TYPE GTC1AC34RA
PROTECTIVE GROUNDING
CLAMP
For Pad Mounted Equipment
A newly designed Protective Grounding
Clamp for making secure connections when
installing Protective Grounding Sets on Pad
Mounted Equipment.
Features a 90° right angle side entry for fer-
rule. Cable connection will now exit clamp
parralel with grounding bar allowing cable set
to remain within the cabinet. Closing the cabi-
net doors will now be easier and will not
require infringing on the safety clearance zone.
Eliminates awkward hotstick mounting and
tightening of clamp jaws from elevated
angles. Improves safety thanks to easier
respect of minimum approach distance.
The clamp is used as a base for new ground-
ing sets or can be retrofit on most grounding
sets for pad mounted equipment.
Designed and manufactured in the U.S.A.
Catalog Number:
GTC1AC34RA
Features
• ASTM classification (F855-04):
– Grade 3 (27kA for 15 cycles)
– Class A/Type I/C-shape
– Brass alloy
– Weight: 1.85 Lbs.
• Jaw range: round section conductor 3/8
to 3/4 diameter.
3.63
[92]
5.15
[131]
5.14
[128]
.32
[8]
1.75
[44]
Conductor groove will accept a
decimal range of 3/8 to 3/4
.645 diameter plain hole to receive standard
5/8 - 11 UNC threaded ferrules
Single phase configuration
(using standard hardware)
Triple phase configuration
(using a 4-way connector)
Possible base for