Página 394 - BURNDY

Versión de HTML Básico

US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
Blue highlighted items are industry standard and most frequently ordered.
BURNDY
®
Overhead
H-17
TYPE LSC
CATCHER
For Aluminum and ACSR
Primary Covered Conductor
(Tree Wire)
Cast aluminum lightning shield clamp with a
galvanized steel eye bolt for use on covered
aluminum and ACSR primary overhead
distribution conductors (“Tree Wire”).
They are designed to protect the “Tree Wire”
from burn-down causing service interruption
during high lightning activity. For further
application details contact the factory.
Conductor groove is pre-filled with PENE-
TROX™ A13, which is compatible with cable
insulation and individually bagged.
Approx. assembly length over eyebolt with cable
clamped. Also approx. eyebolt position when shipped.
Assembly can be installed using a shotgun hotstick as
shown. Assembly instructions are supplied with each
connector.
Catalog
Accommodates
Number
Cable
Cable Dia. “A”
Insul. Dia. “B” (Max.)
“L”
LSC1/0
1/0 Str. AAC - 1/0 ACSR
.368 - .398
.65
4.5
LSC1/0-1
1/0 Str. AAC - 1/0 ACSR
.368 - .398
.83
4.5
LSC556
4/0 Str. - 556.5 AAC
.528 - .858
1.16
5.9
LSC556-1
4/0 Str. - 556.5 AAC
.528 - .858
1.34
5.9