Página 48 - BURNDY

Versión de HTML Básico

A-40
Mechanical
BURNDY
®
Canada: 1-800-387-6487
www.burndy.com
US: 1-800-346-4175
Blue highlighted items are industry standard and most frequently ordered.
U-BLOK™ MOUNTING
PLATFORMS
For Trough Applications
Hole pattern shown is for reference only.
* Supercedes TBPT4/0-6 and TBPT350/500-6.
FLEXI-TAP™
ALLOWABLE AMPACITIES OF INSULATED CONDUCTOR, 60° TO 90° C **
**
NOTE:
Values referenced from Article 310 of the National
Electric Code, Table 310-16, 1996. The above chart is to
be used for REFERENCE ONLY. Please consult Table 310-
16 of the National Electric Code (latest revision) for infor-
mation regarding insulation type, voltage range, and con-
ductor housings/surroundings. U-TAP™, U-BLOK™, and
SPEC-BLOK™ connectors are rated for 90 deg. C by
Underwriters' Laboratories. Use of 60 deg. C and 75 deg. C
conductor(s) is valid, though only as determined by the
National Electric Code.
CATALOG
GUTTER
WEIGHT
NUMBER
W
L
H
SIZE
EACH
TBPT-6*
4-1/4
5-7/8
1-1/2
6
3/4 lb.
TBPT-8
4-1/4
7-7/8
3-1/2
8
1-1/4 lb.
TBPT-10
4-1/4
9-7/8
4
10
1-1/2 lb.
TBPT-12
4-1/4
11-7/8
4
12
1-3/4 lb.
Size AWG
Copper
Al or Copper Clad Al
kcmil
60 deg. C
75 deg. C
90 deg. C
60 deg. C
75 deg. C
90 deg. C
12
25
25
30
20
20
25
10
30
35
40
25
30
35
8
40
50
55
30
40
45
6
55
65
75
40
50
60
4
70
85
95
55
65
75
3
85
100
110
65
75
85
2
95
115
130
75
90
100
1
110
130
150
85
100
115
1/0
125
150
170
100
120
135
2/0
145
175
195
115
135
150
3/0
165
200
225
130
155
175
4/0
195
230
260
150
180
205
250
215
255
290
170
205
230
300
240
285
320
190
230
255
350
260
310
350
210
250
280
400
280
335
380
225
270
305
500
320
380
430
260
310
350
600
355
420
475
285
340
385
700
385
460
520
310
375
420
750
400
475
535
320
385
435