TYPE YFS-CPL
LONG LIMITER ASSEMBLY
With DURICOMP™ Shell and
Rubber Sleeve for Paper-Lead
Cables
The Long Limiter performs the same func-
tions as the Limiter shown on opposite page.
It differs in that it has extra long cable sock-
ets which are preferred by some for use on
paper insuated cable. The end seams are
sealed to make the sockets oil tight. Fusing
characteristics of the Limiter are shown in
technical section. For proper HYPRESS™
installation, see table below.
For conductor sizes not listed call customer service.
To specify a fast acting limiter in any configuration insert an
“F” before the conductor number (example: YFSF34CR
specifies and 1/2 thick limiter section).
Installation Information
Dimensions in Inches
HYPRESS™ and Indentor
Max. Cable
Y34A
Y34BH
Y44B
Dia. Over
with
with
with
Cable
Catalog
Insul.
Y34PR Y34PR
Y44PR Number of
App. Ship
Size
Number
A
L
O.D.
Nest Die
Indents
Wt. in Lbs.
4/0 Str.
YFS28CPL
1
12-3/4 1-15/16
A28D
B28D
E28D
1
1.5
250 kcmil
YFS29CPL
1
12-3/4 1-15/16
A29P
B29D
E29D
1
1.5
300 kcmil
YFS30CPL
1-1/8
13-1/2
2-3/16
A30D
B300
E30D
2
2.2
350 kcmil
YFS31CPL
1-1/8
13-1/2
2-3/16
A31D
B31D
E31D
2
2.2
400 kcmil
YFS32CPL
1-1/8
13-1/2
2-3/16
A32D
B32D
E32D
2
2.3
No Nest
500 kcmil
YFS34CPL
1-11/32
15-7/8
2-3/8
A34D
Die
E34D
2
3.2
Required
750 kcmil
YFS39CPL
1-1/2
15-9/16 2-9/16
— — E39D
2
4.1
K-44
Blue highlighted items are industry standard and most frequently ordered.
Canada: 1-800-387-6487
www.burndy.com
US: 1-800-346-4175