Página 586 - BURNDY

Versión de HTML Básico

TYPES YFAR, YFAP
LIMITER LUG
For Use with Limiter Lug
Assembly
The Limiter Lug incorporates an accurately
determined fusible section as an integral part
with its terminal end. The fusible section is so
selected that it wil prevent the cable from
roasting or damage from a short circuit,
although it will not clear on minor overloads
of short duration not harmful to cable insula-
tion. For proper HYPRESS™ installation, see
table below.
For conductor sizes not listed call customer service.
Dimensions in Inches
Installation Information
For Use on
HYPRESS™ &
Paper Insul.
Indentor Die
For Use on Cable-Oil
Y34A Y34BH Y44B
App.
Rubber Insul. Tight Cable
with with with
Wt.
Cable
Cable
Socket
Y34PR Y34PR Y44PR No. of
in
Size
Catalog No. Catalog No.
B
C
D
L
N T Y O.D.
Nest Die
Indents Lbs.
4/0 Str.
YFAR28-2 YFAP28-2
1-7/8
1 2-3/16 8-1/4 7/16 9/64 27/32 11/16 A28D B28D E28D 1
.28
250 kcmil
YFAR29-2 YFAP29-2
1-7/8 1-1/8 2-3/16 8-1/4 7/16 5/32 27/32 3/4 A29D B29D E29D 1
.33
300 kcmil
YFAR30-2 YFAP30-2
2 1-3/16 2-5/16 8-7/8 1/2 5/32 1 13/16 A30D B30D E30D 2
.42
350 kcmil
YFAR31-2 YFAP31-2
2 1-5/16 2-5/16 8-7/8 1/2 3/16 1
7/8 A31D B31D E31D 2
.46
400 kcmil
YFAR32-2 YFAP32-2
2-1/8 1-7/16 2-5/16 9
1/2 3/16 1 31/32 A32D B32D E32D 2
.55
No Nest
500 kcmil
YFAR34-2 YFAP34-2
2-9/16 1-1/2 2-3/4 10
1/2 7/32 1 1-1/16 A34D
Die Req’d.
E34D 2
.83
750 kcmil
YFAR39-2 YFAP39-2
2-1/2 1-15/16 2-3/4 10
1/2 1/4 1 1-5/16 — — E39D 2
1.2
K-49
Blue highlighted items are industry standard and most frequently ordered.
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
BURNDY
®
Underground