Página 592 - BURNDY

Versión de HTML Básico

BURNDY
®
Underground
US: 1-800-346-4175
www.burndy.com
Canada: 1-800-387-6487
Blue highlighted items are industry standard and most frequently ordered.
K-55
TYPE VYFT
LIMITER TAP ASSEMBLY
For Insulated Cables
The Limiter Tap is suitable for making Limiter
connections to a cable ring bus in a manhole
or transformer vault. It can be installed on oil-
impregnated, paper insulated, or rubber insu-
lated cable. Fusing characteristics of the
Limiter are the same as Type YFA shown in
the technical section. The rubber sleeve and
insulating hood reduce taping to a minimum.
Catalog Numbers shown include hoods. If no
hood is required, eliminate one “C” from the
Catalog Number. Replaceable Link Limiter
Taps can be ordered. For proper HYPRESS™
installation, see table below.
Paper-Lead Cables
If a long cable socket is preferred for use on
paper insulated cable add “L” to the catalog
number (e.g., VYFT3428CCP becomes
VYFT3428CCPL).
Installation Information
For Use on
HYPRESS™ &
Paper Insul.
Indentor Die
For Use on Cable-Oil
Dimensions in Inches
Y34A Y34BH
App.
Rubber Insul. Tight Cable B Max.
BB Max.
with with
Ship.
Cable Size
Cable
Socket
Cable Dia.
Cable Dia.
Y34PR Y34PR No. of Wt. in
A Run AA Tap Catalog No.
Catalog No. Over Insul. Over Insul.
H L
Y
O.D.
Nest Die
Indents Lbs.
500 kcmil
4/0 Str.
VYFT3428CCR VYFT3428CCP
1-3/32
1
4 12-3/16 1-3/4 1-15/16 A28D B28D
1
2.2
No Nest
500 kcmil
500 kcmil
VYFT3434CCR VYFT3434CCP
1-3/32
1-11/32
4 14-3/16 1-3/4 2-3/8 A34D
Die Req’d.
2
3.5
No Nest
750 kcmil
500 kcmil
VYFT3934CCR VYFT3934CCP
1-5/16
1-11/32
4 14-3/16 1-3/4 2-3/8 A34D
Die Req’d.
2
3.7
No Nest
1000 kcmil 500 kcmil
VYFT4434CCR VYFT4434CCP
1-1/2
1-11/32 4-1/8 14-3/16 2-3/32 2-3/8 A34D
Die Req’d.
2
4.0
TYPE NYFT
LIMITER TEE TAP
For Rubber or Paper
Insulated Cables
The NYFT Limiter is similar to Type VYFT
except the run conductor is clamped with a
four bolt cap and the Limiter Tap is removable
by means of a socket and nut assembly.
The Limiter current characteristics are the
same as Type YFA shown in the technical
section.
To specify a fast acting limiter in any configuration insert an
“F” before the conductor number (e.g., YFSF34CR specifies a
1/2 thick limiter section).