Página 685 - BURNDY

Versión de HTML Básico

Substation — Welded/EHV
BURNDY
®
Canada: 1-800-387-6487
www.burndy.com
US: 1-800-346-4175
Blue highlighted items are industry standard and most frequently ordered.
M-36
BOLTED BUNDLED
CABLE SPACER
(Three Conductor)
S3GBP-A
Bolted type
Application: Cable to Cable Spacer
(three cables)
EHV RATED: SELF-SHIELDING
UP TO 550 kV
Material: Cast 356 Aluminum Alloy
Hardware: Aluminum Alloy
Cable Range
Cable Dia.
Catalog Number
AAC
ACSR
Min.
Max.
“J” Dia.
795 kcmil 37 Str. (1.026 Dia.)
715 kcmil 24/7 Str. (1.036 Dia.)
1.026
1.092
5/8’-11 1-1/2” LG.
S3GBP41A
874.5 kcmil 61 Str. (1.077 Dia.)
715.5 kcmil 26/7 Str. (1.051 Dia.)
[26]
[28]
Alum. Alloy
795 kcmil 24/7 Str. (1.092 Dia.)
1.092
1.165
S3GBP44A
954 kcmil 61 Str. (1.126 Dia.)
795 kcmil 54/7 Str. (1.093 Dia.)
[28]
[30]
1033.5 kcmil 37 Str. (1.170 Dia.)
954 kcmil 45/7 Str. (1.165 Dia.)
1.165
1.246
S3GBP445A
1113 kcmil 61 Str. (1.216 Dia.)
1033.5 kcmil 45/7 Str. (1.213 Dia.)
[30]
[32]
5/8”-11 1-3/4” LG.
1192 kcmil 61 Str. (1.258 Dia.)
1033.5 kcmil 54/7 Str. (1.246 Dia.)
1.246
1.382
Alum. Alloy
S3GBP45A
1272 kcmil 61 Str. (1.300 Dia.)
1192.5 kcmil 54/19 Str. (1.333 Dia.)
[32]
[35]
1590 kcmil 61 Str. (1.453 Dia.)
1272 kcmil 54/19 Str. (1.382 Dia.)
1.382
1.504
S3GBP46A
1600 kcmil 127 Str. (1.454 Dia.)
1431 kcmil 54/19 Str. (1.465 Dia.)
[35]
[38]
1750 kcmil 127 Str. (1.526 Dia.)
1590 kcmil 45/7 Str. (1.502 Dia.)
1.504
1.632
S3GBP48A
2000 kcmil 91 Str. (1.630 Dia.)
1750 kcmil 84/19 Str. (1.602 Dia.)
[38]
[41]
2000 kcmil 91 Str. (1.630 Dia.)
1890 kcmil 84/19 Str. (1.650 Dia.)
1.632
1.737
5/8”-11 2” LG.
S3GBP483A
2250 kcmil 91 Str. (1.729 Dia.)
2167 kcmil 72/7 Str. (1.737 Dia.)
[41]
[44]
Alum Alloy
2300 kcmil 61 Str. (1.750 Dia.)
2167 kcmil 72/7 Str. (1.737 Dia.)
1.737
1.824
S3GBP486A
2500 kcmil 127 Str. (1.823 Dia.)
2156 kcmil 84/19 Str. (1.762 Dia.)
[44]
[46]
NOTES:
1. Dimensions in brackets [ ] are in millimeters.
2. For stainless steel hardware add SUFFIX “SS” to catalog
number (example: S3GBP48ASS).
3. For variations in cable spacing contact factory.
4. For four hole straight pad tap or 90° version or bus sup-
port three bundled cable spacer, contact the factory.