H-75
Elastimold
®
Molded Canister Fuses (MCAN)
Power & High Voltage —
Elastimold
®
& Hi-Tech
®
Fuse Products
Fuse Ratings
Nominal Voltage Rating (kV)
8.3
15.5
23.0
Rated Maximum Voltage (kV)
8.8/10.0 15.5/17.2**
23.0
Frequency (Hz)
50–60
50–60
50–60
Current Rating (Amps)
3–80
3–65
6–50
Rated Maximum Interrupting
50,000
50,000
50,000
Current (Sym. Amps)
Fuse Canister Ratings
System Voltage Class (kV)
15
25/28
Maximum Line-to-Ground Voltage (kV)
8.8/10.0
15.5/17.2
BIL Impulse Withstand (kV)
95
125/140
One-Minute AC Withstand (kV)
34
40–45
Fifteen-Minute DC Withstand (kV)
53
78
Corona Extinction (kV)
11
19–21.5
Maximum Continuous Current (Amps)
200*
200*
Momentary Current (kA)
10*
10*
The MCAN Molded Canister Fuse is a compact, lightweight EPDM molded rubber fuse enclosure package. MCAN fuse canisters are maintenance-free,
completely sealed and submersible. Designs are deadfront, using molded rubber to insulate, shield and eliminate exposed live parts. Units are ideally suited
for padmount, subsurface or vault applications, for systems through 28kV gndY–gndY. The MCAN Molded Canister Fuse will accommodate and has been
thoroughly tested with Hi-Tech
®
Trans-Guard
®
FX fuses. Contact Thomas & Betts before using fuses from other manufacturers.
Completely sealed and insulated
for padmount, subsurface or vault
applications through 28kV gndY–gndY.
MCAN Molded Canister Fuse
EPDM molded rubber deadfront construction insulates,
shields and eliminates live parts
Fuses are fully sealed and submersible
Modular construction enables elbow connection or direct
attachment to equipment-mounted bushings
Neon voltage indicators (V2) attached to elbow test points
to provide quick and convenient blown-fuse indication
Various end fittings and bushings make for flexible installation
on switchgear, junctions, transformers, cable runs and taps
Replaceable fuse enables easy fuse replacement without full removal from installation
Current-limiting protection limits the system available fault current and dramatically reduces stresses on equipment
304 stainless steel mounting brackets and wall-mounted parking stands available to accommodate a wide variety
of mounting arrangements
Certified Tests
Elastimold
®
Molded Canister Fuses have been designed and tested
per applicable portions of IEEE, ANSI, NEMA and other industry
standards, including:
ANSI C37.40
Standard for Current-Limiting Fuse Service Conditions
ANSI C37.41
Standard for Current-Limiting Fuse Design & Testing
ANSI C37.47
Standard for Current-Limiting Fuse Ratings & Specifications
ANSI/IEEE 386
Standard for Separable Connectors & Bushing Interfaces
Application Information
Construction: Submersible, corrosion resistant, fully shielded
Ambient Temperature Range: -30° C to 65° C
* Without fuse.
** The 15.5kV L-G rated fuses require at least 75% grounded load
to be applied on a 25kV system.
Note