Página 36 - elastimold

Versión de HTML Básico

www.tnb.com
United States
Tel: 901.252.8000
800.816.7809
Fax: 901.252.1354
Technical Services
Tel: 888.862.3289
H-96
Hi-Tech
®
FX Series Full-Range Current-Limiting Fuses
Power & High Voltage —
Elastimold
®
& Hi-Tech
®
Fuse Products
Dimensional Information for Trans-Guard
®
FX Fuses
Nominal Fuse
Voltage Rating (kV)
Current Rating
(Amps)
Dimensions inches (mm)
Standard
Mounting Code
A
B
C
5.5
3–75
2.25–2.18"
(57.0–55.3mm)
10.00–9.90"
(254.0–251.5mm)
1.02–1.00"
(25.9–25.4mm)
4
80–200
3.32–3.25"
(84.4–82.5mm)
17.51–17.35"
(444.8–440.7mm)
1.21–1.17"
(30.7–29.7mm)
6
8.3
3–50
2.25–2.18"
(57.0–55.3mm)
10.00–9.90"
(254.0–251.5mm)
1.02–1.00"
(25.9–25.4mm)
4
65–80
2.25–2.18"
(57.0–55.3mm)
14.31–14.21"
(363.5–360.9mm)
1.02–1.00"
(25.9–25.4mm)
5
65–125
3.32–3.25"
(84.4–82.5mm)
14.70–14.54"
(373.4–369.3mm)
1.21–1.17"
(30.7–29.7mm)
5
15.5
3–50
2.25–2.18"
(57.0–55.3mm)
14.31–14.21"
(363.5–360.9mm)
1.02–1.00"
(25.9–25.4mm)
5
65
2.25–2.18"
(57.0–55.3mm)
17.12–17.02"
(434.8–432.3mm)
1.02–1.00"
(25.9–25.4mm)
6
65–100
3.32–3.25"
(84.4–82.5mm)
17.51–17.35"
(444.8–440.7mm)
1.21–1.17"
(30.7–29.7mm)
6
23.0
6–50
2.25–2.18"
(57.0–55.3mm)
17.12–17.02"
(434.8–432.3mm)
1.02–1.00"
(25.9–25.4mm)
6
“ ”
“ ”
“ ”
Blown Fuse Indicator — Type 1
Before Operation
After Operation
Construction
Low Current Interruption
Element (Includes Patented
Damage Sensor
Tin-Plated
Brass Caps
A
Solid
Electrical
Connection
and Sealing
Resin-Rich Filament Wound
Glass/Epoxy Body
Compacted
Quartz Sand
Length B
Welded
Element Joints
Mica
Element
Support
High Current
Interruption Element
Epoxy
Joint
(Both
Ends)
.625
(15.9)
C