H-105
Hi-Tech
®
SX Series Full-Range Current-Limiting Fuses
Power & High Voltage —
Elastimold
®
& Hi-Tech
®
Fuse Products
Nominal
Fuse Voltage
Rating (kV)
Current
Rating
(Amps) (2)
Fuse
Cat. No.
Rated
Maximum
Voltage (kV)
Maximum Continuous
Current (in Oil @ 60° C) (5)
Peak Arc
Voltage
(6) (kV)
Minimum
Melt I
2
t
(AMP
2
-SEC)
Maximum
Melt I
2
t (3) (4)
(AMP
2
-SEC)
5.5
100
HTSX320100
5.5
114.0
15
22,100
110,000
150
HTSX320150
147.0
56,700
280,000
175
HTSX320175
172.0
78,300
380,000
225
HTSX320225
230.0
176,000
860,000
250
HTSX320250
253.0
259,000
1,270,000
8.3
5
HTSX230005
10.0
5.0
30
100
350
10
HTSX230010
11.5
32
620
2,700
12
HTSX230012
14.0
28
800
4,000
15
HTSX230015
17.0
28
800
4,000
20
HTSX230020
22.5
26
920
8,000
25
HTSX230025
25.0
26
1,310
9,500
30
HTSX230030
30.0
26
1,620
11,000
40
HTSX230040
43.0
26
3,660
22,000
50
HTSX230050
53.0
26
5,250
30,000
65
HTSX230065
65.0
26
8,700
50,000
75
HTSX230075
75.0
26
12,800
70,000
90
HTSX330090
8.3
92.0
25
25,200
100,000
100
HTSX330100
105.0
47,500
185,000
150
HTSX330150
150.0
78,300
330,000
160
HTSX330160
163.0
115,150
480,000
15.5
5
HTSX240005
17.2
5.0
51
100
510
10
HTSX240010
11.5
54
620
2,600
12
HTSX240012
14.0
46
800
3,700
15
HTSX240015
17.0
46
800
3,700
20
HTSX240020
22.5
43
920
6,500
25
HTSX240025
25.0
45
1,310
8,000
30
HTSX240030
30.0
45
1,620
10,000
40
HTSX240040
43.0
45
3,660
22,000
50
HTSX240050
53.0
45
5,250
30,000
65
HTSX240065
65.0
45
8,700
50,000
75
HTSX240075
75.0
45
12,800
70,000
90
HTSX340090
15.5
98.0
40
25,200
110,000
100
HTSX340100
117.0
39,400
185,000
150
HTSX340150
150.0
80,000
380,000
23.0
10
HTSX250010
23.0
11.5
67
620
3,100
12
HTSX250012
14.0
61
800
4,800
15
HTSX250015
17.0
61
800
4,800
20
HTSX250020
22.5
60
920
8,300
25
HTSX250025
25.0
60
1,310
11,200
30
HTSX250030
30.0
60
1,620
13,000
40
HTSX250040
42.0
60
3,660
28,000
50
HTSX250050
51.0
60
5,250
38,000
65
HTSX250065
65.0
60
8,700
61,000
Electrical Characteristics of Trans-Guard
®
SX Fuses
Notes:
1. Designs have a 50,000 amps RMS. Symmetrical Rating (except 5A 17.2kV which was tested at 44kA maximum).
2. Fuses rated 75A and below are 2.25" in diameter. Higher ratings are 3.3" in diameter.
3. Tabulated Maximum Total I
2
t values are for currents of 50,000 amperes at the nominal voltage of the fuse. Fuses which have a Rated Maximum Voltage higher than their Nominal Voltage
Rating will have a higher I
2
t let-through when applied at voltages up to these higher values. For example, Maximum Total I
2
t values are increased by approximately 30% when 8.3kV fuses
are applied at 10kV and approximately 25% when 15.5kV fuses are used at 17.2kV.
4. Maximum total I
2
t values are reduced for currents below 50,000A. For example, at 10,000A, I
2
t values are approximately 15% less than the published values.
5. Maximum continuous currents at different ambient temperatures: These may be determined by derating the fuses by .2% per degree C over 60° C (for example at 80° C the derating would
be 20 x .2 = 4%, making the maximum continuous current of a 20 A fuse 22.5 x .96 = 21.6A) or rerating the fuses by .2% per degree C under 60° C (for example, at 40° C the rerating
would be 20 x .2 = 4%, making the maximum continuous current of a 20 A fuse 22.5 / .96 = 23.4A). The long time melting current of the fuses (approximately one hour and longer) due to
different ambient temperatures is the same as described above for “Maximum Continuous Currents”. See time current characteristics for melting characteristics in this time region.
6. Peak arc voltages quoted are for 50,000A currents at the rated maximum voltage listed. Reduced currents and voltages will reduce the peak arc voltage.
Consult the factory for further information.