SX Series Full-Range Current-Limiting Fuses
Power & High Voltage —
Elastimold
®
& Hi-Tech
®
Fuse Products
Continuous
Current Rating
(Amps)
CaT. No.
5.5kV
8.3kV
15.5kV
23.0kV
5
HTSX230005
HTSX240005
10
HTSX230010
HTSX240010
HTSX250010
12
HTSX230012
HTSX240012
HTSX250012
15
HTSX230015
HTSX240015
HTSX250015
20
HTSX230020
HTSX240020
HTSX250020
25
HTSX230025
HTSX240025
HTSX250025
30
HTSX230030
HTSX240030
HTSX250030
40
HTSX230040
HTSX240040
HTSX250040
50
HTSX230050
HTSX240050
HTSX250050
65
HTSX230065
HTSX240065
HTSX250065
75
HTSX230075
HTSX240075
90
HTSX330090
HTSX340090
100
HTSX320100
HTSX330100
HTSX340100
150
HTSX320150
HTSX330150
HTSX340150
160
HTSX330160
175
HTSX320175
225
HTSX320225
250
HTSX320250
Note:
To order a 15.5kV fuse that will fit in an 8.3kV wet-well fuseholder, replace the 7th character (“0”) in the catalog number with a “2” (example: HTSX242050).
Ordering Information for Trans-Guard
®
SX Fuses
Trans-Guard
®
SX Fuse Ordering Information
To order the proper fuse for a particular application, first determine the correct fuse voltage and current rating using
the published performance data (
page H-105
). Then refer to the chart below to determine the appropriate catalog number.
Alternatively, fuse selection can be determined using the accompanying charts on
pages H-106–H-107
.
When replacing the obsolete AB Chance SL fuse with a Hi-Tech
®
Fuses
Trans-Guard
®
SX fuse, it is important to recognize that the SX fuse designs
should not be used on distribution systems where the primary line-to-line voltage
exceeds the rated maximum voltage of the fuse as shown in the chart to the right:
This should be considered when choosing a proper replacement for the AB Chance
SL fuse as they were, in some cases, used on systems having line-to-line voltages
greater than that of the current-limiting fuse component of the assembly.
Again, when choosing the appropriate Hi-Tech SX fuse to replace the AB
Chance SL fuse, care must be taken to ensure that the rated maximum voltage
of the SX fuse exceeds the system line-to-line voltage. The only exception to this
requirement is when all the transformers that are downstream from the switches
where the SX fuses are to be installed are GndY-GndY connected with less than
50% delta connected secondary load. In that case, a fuse having a rated maximum
voltage exceeding the system line-to-neutral voltage may be used.
Trans-Guard
®
SX
Nominal
Fuse Voltage
Rating (kV)
Current
Rating
(Amps)
Rated
Maximum
Voltage (kV)
5.5
100–250
5.5kV
8.3
5–75
10.0kV
90–160
8.3kV
15.5
5–75
17.2kV
90–150
15.5kV
23.0
10–65
23.0kV
Important Notice When Using Trans-Guard
®
SX Fuses