CABLE ACCESSORIES
Elastimold Separable Connectors, Cable Joints,
Cable Terminators and other cable accessory
products have been designed and tested per
applicable portions of IEEE, ANSI and other
industry standards including:
• IEEE 386™ Standard For Separable Connectors
• IEEE 404™ Standard For Cable Joints and Splices
• IEEE 48™ Standard For Cable Terminations
• IEEE 592™ Standard For Exposed
Semiconducting Shields
• ANSI C119.4 Standard For Copper and Aluminum
Conductor Connectors
• AEIC CS8 Standards For XLP and EPR
Insulated Cables
• ICEA S-94-649-2004 and S-97-682-2000 Standard
for Cables Rated 5,000 – 46,000 Volts
A i
ion nform ion:
1. Loadbreak connectors are designed and rated for use on grounded WYE systems. For application on ungrounded WYE or delta systems, the
next higher voltage class product is recommended. Examples: 5kV ungrounded: use 15kV class products; 15kV ungrounded: use 25kV class
products; 25kV ungrounded: use 35kV class products.
2. Products are designed and constructed for all applications including padmount, subsurface, vault, indoor, outdoor, direct sunlight, direct buried
and continuously submerged in water.
3. Products are designed and rated for ambient temperatures of -40° C to +65° C. It is recommended that loadbreak connectors be hotstick
operated at -20° C to +65° C ambient temperature range and at altitudes not exceeding 6000 feet.
TABLE
5kV Class atings
25kV Class atings
35kV Class atings
• PE AT G V LTAGE
8.3kV
15.2kV
21.1kV
Maximum line-to-ground
(See Application Info Note 1)
• B L
Impulse withstand 1.2 x 50 microsecond wave
95kV
125kV
150kV
• W THSTA D V LTAGE
AC One Minute
34kV
40kV
50kV
DC Fifteen Minute
53kV
78kV
103kV
• C A EXT CT LEVEL
@ 3pC Sensitivity
11kV
19kV
26kV
200 A P Products
Continuous Current:
200 AMP*
Symmetrical Momentary Current:
10kA sym, 10 cycle duration
600 Series Products
Continuous Current:
600 and 900 AMP*
Symmetrical Momentary Current:
25kA sym, 10 cycle duration
* Designed for 90° C maximum continuous operating temperature
CABLE J TSA D TE AT S AT GS
Refer to the pages listed below for rating information:
• PCJ Cable Joints, page 22.
• Cable Terminations, page 24.
SEPA ABLE C ECT AT GS
Table 1 shows voltage and current ratings which apply to all Separable Connectors including 200 AMP Loadbreak, 200
AMP Deadbreak and 600 Series Deadbreak products. Table 2 shows switching and fault close ratings which only apply
to 200 AMP Loadbreak Connectors.
TABLE 2
L AD AKE/L ADB EAK SW TCH G
AULT CL SE
• 1ø and 3ø circuits 8.3kV line to ground, 14.4kV
max. across open contacts.
• 10 loadmake/break operations at 200 Amps max.
with 70 to 80% lagging power factor.
• 1ø and 3ø circuits 15.2kV line to ground, 26.3kV
max. across open contacts.
• 10 loadmake/break operations at 200 Amps max.
with 70 to 80% lagging power factor.
• 1ø and 3ø circuits 21.1kV line to ground, 36.6kV
max. across open contacts.
• 10 loadmake/break operations at 200 Amps max.
with 70 to 80% lagging power factor.
1 fault close operation at 8.3kV or 14.4kV; 10,000
Amps, rms, sym. 10 cycles (0.17 sec.) 1.3 max.
asym factor applies to new or used mating parts
(up to maximum designated switching operations.)
1 fault close operation at 15.2kV or 26.3kV; 10,000
Amps, rms, sym. 10 cycles (0.17 sec.) 1.3 max.
asym factor applies to new or used mating parts
(up to maximum designated switching operations.)
1 fault close operation at 21.1kV or 36.6kV; 10,000
Amps, rms, sym. 10 cycles (0.17 sec.) 1.3 max.
asym factor applies to new or used mating parts
(up to maximum designated switching operations.)
5kV
Class atings
25kV
Class atings
35kV
Class atings
Certified Tests and
Performance
Ratings