Página 66 - elastimold

Versión de HTML Básico

CABLE ACCESSORIES
Separable Connectors
600 Series Deadbreak
INTEGRAL BUSHING
RETAINING
RING
CABLE TO EQUIPMENT
COMPRESSION
LUG
CABLE
ADAPTER
CABLE TO CABLE
STRAIGHT RECEPTACLE
HOUSING
LOADBREAK
ELBOW
TAP PLUG
200A LOADBREAK
SEE PAGES 4, & 5
200A DEADBREAK
SEE PAGES 8 & 9
LINK-OP
LINK CONNECTOR
SPANNER WRENCH
OPERATING
ACCESSORIES
4 PT JUNCTION
3 PT JUNCTION
2 PT JUNCTION
(UTILIZING JUNCTIONS)
HOTSTICK OPERABLE 600 SERIES
CONNECTORS - SEE PAGES 14 - 17
STICK-OP
LINK-OP
COMPRESSION
LUG
CABLE
ADAPTER
VAULT
STRETCHER
CONNECTOR
CABLE TO CABLE
L-1
UTILIZING L-KITS
L-2
ELBOW CONNECTOR
STICK-OP
LOADBREAK REDUCING
TAP PLUG
BOLT &
WASHERS
STRAIGHT
RECEPTACLE ADAPTER
L-3
L-4
THREADED
STUD
LINK-OP
RETAINER
SLEEVES
200A TAPS
INSULATING
PLUG
INSULATED
PARKING BUSHING
BUSHING
EXTENDER
THREADED
COMPRESSION
LUG
600 SERIES
ELBOW
CABLE
ADAPTER
COMPRESSION
LUG
CONNECTING
PLUG
STRAIGHT RECEPTACLE
REDUCING TAP
WELL
THREADED
STUD
VOLTAGE
DETECTION
CAP
INSULATED CAP
WITH TEST POINT
GROUNDING
PLUG
DEADBREAK
REDUCING
TAP PLUG
600 SERIES
TAPS
CAM-OP
RETAINER
SLEEVES
CONNECTING
PLUG
VAULT
STRETCHER
BUSHING
EXTENDER
THREADED
STUD
THREADED
STUD
WINDOW-OP
SEE PGS 16 &17
CAM-OP
CABLE
ADAPTER
COMPRESSION
LUG
CAM-OP
LINK CONNECTOR
SEE PGS 14 & 15
SEE PGS 14 & 15
SEE PGS 16 & 17
VS2
VS3
VS4
VAULT STRETCHERS
CABLE TO CABLE UTILIZING
600 Series deadbreak elbows,
straight receptacles, junctions, vault
stretchers and accessories are used
to connect equipment and cable on
primary feeder and network circuits.
Designs accommodate large conduc-
tors and feature bolted connections
and deadfront modular construction
for maximum reliability, perfor-
mance and versatility.
DE-ENERGI ED connectors can be
quickly and easily connected and
disconnected using standard hand
tools and equipment in accordance
with accepted operating practices.
Optional accessories allow visible ex-
ternal separation, by-pass, isolation,
dead-ending, grounding, and testing
as well as adding taps, surge arrest-
ers and circuit protection.
Hotstick operable and separable
joint systems are shown on pages 14
thru 19.
AT GS VE V EW
See page 2 for complete information.
CU E T AT GS
(Prefixes: 650, K650, K655, K656,
750, 755, 756 & 03700)
600 Amp Continuous
25kA sym.,10 cycles
(Prefixes 675,K675,K676,775,
776 & 03702)
900 Amp Continuous
25kA sym.,10 cycles
NOTE: 900 Amp ratings require copper cable
and copper current-carrying components.
Vo r in
5/25kV Class (5kV thru 28kV)
16.2kV Phase-to-Ground
28kV Phase-to-Phase
140kV BIL
45kV AC Withstand
84kV DC Withstand
21.5kV Corona Extinction
35kV Class
21.1kV Phase-to-Ground
36.6kV Phase-to-Phase
150kV BIL
50kV AC Withstand
103kV DC Withstand
26kV Corona Extinction
Note: Elastimold has increased the IEEE
Standard Pro uction and Design Test levels for
25kV Class products to include 27kV and 28kV
systems.
SEE PRODUCT GUIDE
PG-PC-E FOR
SURGE ARRESTER
APPLICATIONS
600 Series Deadbreak
SEPA ABLE C ECT S 600 SE ES DEADB EAK