Página 78 - elastimold

Versión de HTML Básico

CABLE ACCESSORIES
Cable Terminations
ELECT CAL AT GS
SU A Y
The following ratings summary is based
on IEEE Std. 48 and applies to all the
terminations on page 24 thru 27. Elastimold
terminations are designed for use on three-
phase systems, either 3-wire or 4-wire and
the single-phase laterals of these systems.
V LTAGE AT GS
5kV Class
9.5kV Phase-to-Ground
110kV BIL 1.2 x 50 microsecond wave
AC Withstand:
 50kV 1 min. – dry
 35kV 6 hr. – dry
 45kV 10 sec. – wet
13kV Corona Extinction
25kV Class
16kV Phase-to-Ground
150kV BIL 1.2 x 50 microsecond wave
AC Withstand:
 65kV 1 min. – dry
 55kV 6 hr. – dry
 60kV 10 sec. – wet
21.5kV Corona Extinction
35kV Class
22kV Phase-to-Ground
200kV BIL 1.2 x 50 microsecond wave
AC Withstand:
 90kV 1 min. – dry
 75kV 6 hr. – dry
 80kV 10 sec. – wet
30kV Corona Extinction
MODULAR TERMINATORS
BRACKETS
35MSC
35MTB
PB-1
16TB2
1535AFB
16THGS
16THG
35MTGI
35MTG
STRESS CONE
35MSCI
PCT-1
PCT-2
SINGLE PIECE TERMINATORS
Elastimold cable terminations are
available in single piece or modular
designs. Terminators allow connec-
tion and transition from shielded, un-
derground cable to bare overhead
conductors and live-front equip-
ment. Units are designed and rated
per IEEE Standard 48 for riser pole,
padmount, indoor and outdoor ap-
plications. PCT1, PCT2, 16THG
and 35MTG terminators provide
sufficient creep, strike and weather
sealing for class 1 outdoor service.
PCT1 and PCT2 also include an in-
tegral cable jacket seal.
The 35MTGI terminators and
35MSC stress cones are rated for
class 2 and class 3 indoor service
respectively. Optional mounting
brackets, aerial lugs and equipment
connectors are available as required.
Cable Terminations