Página 79 - elastimold

Versión de HTML Básico

Cable Terminations
CABLE ACCESSORIES
llustration Description Voltage ELAST LD
otes
(not to scale)
Class Part umber
Single-Piece
15kV
PCT - X-
N12,14,
Terminator
Use Table X9
15,22
(Class 1)
25kV
PCT2- X-
N12,14,
Use Table X9
Housing
15kV
PCT -
N13,22
only
25kV
PCT2-
N13,23
Single-Piece 15/25kV
6THG-WX-
N2,14
Terminator
Use Tables W12 and X8
15
(Class 1)
Housing 15/25kV
6THGH-W
only
Use Table W12
Single-Piece 15/25kV
6THGS-WX
N3
Terminator
Use Tables W12 and X4
for solid
conductor only
(Class 1)
Stress Cone ALL
35 SC-W
N17
(Class 3)
Use Table W11
Stress Cone ALL
35 SC -W
N17
w/Grd. Strap
Use Table W11
Modules
ALL
35 G-W
N11,16
only
Use Table W13
Modular
15kV
35 TG-WX- -CA
N2,11
Terminator
Use Tables W13 and X3
(Class 1)
25kV
35 TG-WX-8-CA
N2,5,11
Use Tables W13 and X3
35kV
35 TG-WX- 0-CA
N2,6,11
Use Tables W13 and X3
Modular
15kV
35 TG -W-
N11
Terminator
Use Table W13
(Class 2)
25kV
35 TG -W-6
N11
w/o Rain
Use Table W13
Cap
35kV
35 TG -W-8
N7,11
Use Table W13
Rod Contact 15/25kV
00700X
N1,14,
for PCT
Use Table X9
15
Rod Contact 15/25kV
6TCA-X
N2, 8
for 16THG
Use Table X8
Solid Conductor 15/25kV
6CAS-X
N3, 9
Package
Use Table X4
for 16THGS
3/4”-16 Threaded ALL
35 TGA-WX-
N2,10,11
Rod for MTG
Use Tables W13 and X3
18, 25
1”-14 Threaded ALL
35 TGA-WX-2
N2,10,11
Rod for MTG
Use Tables W13 and X3A
19, 25
Two-Hole Spade ALL
35 TGA-WX-3
N4,10,11
for MTG
Use Tables W13 and X3
20, 25
Two-Hole Spade ALL
0 000X
N1
for PCT
Use Table X9
One-Hole Spade ALL
0 00X
N1
for PCT
Use Table X9
Universal Rod ALL
35 TGA-WX-
N2,10,11
for MTG
Use Tables W13 and X3
21, 25
Aerial Lugs
ALL
35AL-A
N10, 24
for MTG
Threaded Rod
(Two-hole spade
or bare wire)
TE AT S
N1. Use with PCT1 or PCT2 Terminators.
N2. Includes contact rod, ground strap and rain cap.
N3. Includes crimp ring, ground strap and rain cap.
N4. Includes spade contact, ground strap and rain cap.
N5. For KA thru PB sizes use 35MTG-WX-6-CA.
N6. For KA thru PB sizes use 35MTG-WX-8-CA.
N7. For KA thru PB sizes use 35MTGI-W-6.
N8. Use with 16THG Terminators.
N9. Use with 16THGS Terminators.
N10. Use with 35MTG Terminators.
N11. Refer to page 26 for detailed ordering instructions.
N12. Includes rod contact as standard. Specify suffix “-3” in place of “-4”
for two-hole spade lug. Specify suffix “-5” in place of “-4” for one-
hole spade lug.
N13. Specify suffix “-3” or “-5” in place of “-4” for two-hole spade lug
housing or one- hole spade style housing.
N14. Use 1X for an aluminum rod contact for aluminum conductors only.
N15. Substitute 0X for 1X for a universal aluminum rod contact for
aluminum or copper conductors.
N16. Available in sizes from GA thru PB & are supplied qty.
2 per package.
N17. Available in sizes EB thru PB.
N18. For conductors from 1/0 thru 350 kcmil.
N19. For conductors from 400 kcmil thru 1000 kcmil.
N20. For conductors from #2 to 1000 kcmil.
N21. For conductors from #6 thru 4/0.
N22. Use for insulation dia. range from .640” thru 1.070”.
N23. Use for insulation dia. range from .830” thru 1.180”.
N24. Select symbol for “A” from aerial lug ordering information on
page 26.
N25. W13 Table provides sizing for rain cap.
X10 Table provides sizing for connectors.
15,23
Cable Terminations
Refer to the
W
and
X
tables on pages 38 and 39 for sizing to cable
insulation diameter and conductor size.
For cable shield adapters and jacket seals, see page 28.