Página 83 - elastimold

Versión de HTML Básico

Shield Adapters, Ground-
ing Kits and Jacket Seals
CABLE ACCESSORIES
Illustration
Description
ELASTIMOLD Suffix Notes
(not to scale)
Part umber
Cold Shrinkable
200ECS
-S
N1,3
Jacket Seal
Cold Shrinkable
600ECS
-S
N1,4
Jacket Seal
Metallic Tape
20 A-W -0 A
N1,2,5,6
Shield Adapter
Use Table W14
for sizing
Wire Shield
2 A-W - A
N1,2,5,6
Adapter
Use Table W14
for sizing
Shield
0TL-W
-TL
N1,2
Adapter
Use Table W15
for sizing
Cold Shrinkable Seal
200ECSG -2 -SG
N1,3,5,6
w/ Copper Rod &
Crimp Connector
Cold Shrinkable Seal
600ECSG -2 -SG
N1,4,5,6
w/ Copper Rod &
Crimp Connector
Cold Shrinkable Seal
200ECSG2-2 -SG2
N1,3,5,6
w/ Copper Rod &
Constant Force
Spring
Cold Shrinkable Seal
600ECSG2-2 -SG2
N1,4,5,6
w/ Copper Rod &
Constant Force
Spring
Cold Shrinkable Seal
200ECSG3
-SG3
N1,3,5,7
w/ Copper Braid &
Constant Force
Spring
Cold Shrinkable Seal
600ECSG3
-SG3
N1,4,5,7
w/ Copper Braid &
Constant Force
Spring
N1. To order the kits as separate items, use the part numbers shown in
the table. Example: To order a cold shrinkable tube as a separate
item, use the part number 200ECS.
To order the kits as components of other items, add the suffix to the
end of the part number. Example: To order a cold shrinkable jacket
seal as a component of an elbow kit, use the part number 166LR-
A5200-S.
N2. Only use this suffix with part numbers that designate a “W” housing
size. Sizing the main component will also size the suffix adapter.
N3. Size range .80” to 1.50” jacket diameters. Maximum installed
diameter is approx. 2”.
N4. Size range 1.28” to 2.30” jacket diameters. Maximum installed
diameter is approx. 2.75”.
N5. Voltage rating equal to Elastimold product being used.
N6. Copper rod size is no. 6 for sizes FA thru HA and no. 2 for sizes
HAB thru JB.
N7. Braid is equivalent to no. 6 copper rod for sizes FA thru HA and no.
2 copper rod for sizes HAB thru JB.
nsulation
Table
W 5
nches
Symbol
.
AX.
for W
.495 .585 EB
.525 .635 EF
.575 .585 FA
.625 .735 FAB
.675 .785 FB
.725 .835 FG
.775 .885 GA
.825 .935 GAB
.875 .985 GB
.930 1.040 GH
.980 1.115 HA
1.040 1.175 HAB
1.095 1.240 HB
1.160 1.305 HJ
1.220 1.375 JA
1.285 1.395 JAB
1.355 1.520 JB
1.485 1.595 KA
1.530 1.640 KAB
1.575 1.685 KB
1.755 1.875 PB
USE
0TL
nsulation
Table
W
nches
Symbol
.
AX.
for W
.530 .680
E
.640 .820
F
.760 .950
G
.850 1.050 H
.980 1.180
J
1.090 1.310 K
1.180 1.465 L
1.370 1.630 M
1.515 1.780 N
USE
20 A
2 A
Shield Adapters, Sealing & Grounding