eference
AEIC & ICEA Cable Insulation Diameter
5kV Cable ( 00% level, 75 mil)
Aluminum
& Copper
Conductor
Size
ndustry
Standard
Solid Conductor
Stranded Conductor
Compressed Conductor
Compact Conductor
Diameter in Inches
ver nsulation
Diameter in Inches
ver nsulation
Diameter in Inches
ver nsulation
Diameter in Inches
ver nsulation
in.
Max.
in.
Max.
in.
Max.
in.
Max.
#2
AEIC
0.610
0.700
0.635
0.725
0.620
0.710
ICEA
0.610
0.695
0.645
0.730
0.635
0.720
0.620
0.705
#
AEIC
0.645
0.730
0.675
0.765
0.655
0.740
ICEA
0.645
0.725
0.685
0.770
0.675
0.760
0.655
0.735
/0
AEIC
0.680
0.770
0.715
0.805
0.690
0.775
ICEA
0.680
0.760
0.725
0.810
0.715
0.800
0.690
0.775
2/0
AEIC
0.760
0.850
0.730
0.815
ICEA
0.775
0.855
0.760
0.845
0.730
0.815
3/0
AEIC
0.810
0.900
0.775
0.865
ICEA
0.825
0.905
0.810
0.895
0.775
0.860
/0
AEIC
0.865
0.955
0.830
0.915
ICEA
0.880
0.965
0.865
0.950
0.830
0.910
250
AEIC
ICEA
0.935
1.020
0.920
1.005
0.880
0.965
350
AEIC
1.025
1.115
0.980
1.065
ICEA
1.045
1.130
1.025
1.110
0.980
1.065
500
AEIC
1.150
1.245
1.100
1.185
ICEA
1.175
1.260
1.150
1.235
1.100
1.185
750
AEIC
1.340
1.440
1.280
1.370
ICEA
1.370
1.455
1.340
1.425
1.280
1.365
000
AEIC
1.485
1.590
1.430
1.520
ICEA
1.520
1.610
1.485
1.575
1.430
1.515
W = nsulation Diameter (Conductor + 2 X Conductor Shield + 2 X wall)
ICEA NOTE: Diameters specified in the above table are different than specified by AEIC CS8-00. Consult Accessory Manufac-
turer for proper selection of accessories. Diameters to be measured in accordance with 9.6.
AE C CS8-06
Specification for Extruded Dielectric,
Shielded Power Cable Rated 5 - 46kV
AEIC-Calulated Diameters - Solid and Compressed Stranding from
Tables C-4 & C-6 and Compact Stranding from Tables C-5 & C-7
A S / CEA S-9 -6 9-200 & S-97-682-2000
Standard for Concentric Neutral Cables &
Utility Shielded Power Cables Rated 5 - 46kV
ICEA-Concentric Stranding Table C-3, Compressed Stranding
Table C-4, Compact Stranding Table C-5
ICEA Abbreviated, for additional cables please refer to the standard.
15kV 100% – 175 mil Insulation (.175”)
15kV 133% – 220 mil Insulation (.220”)
25kV 100% – 260 mil Insulation (.260”)
35kV 100% – 345 mil Insulation (.345”)
WALL