CABLE ACCESSORIES
eference
AEIC & ICEA Cable Insulation Diameter
35kV Cable ( 00% level, 3 5 mil)
Aluminum
& Copper
Conductor
Size
ndustry
Standard
Solid Conductor
Stranded Conductor
Compressed Conductor
Compact Conductor
Diameter in Inches
ver nsulation
Diameter in Inches
ver nsulation
Diameter in Inches
ver nsulation
Diameter in Inches
ver nsulation
in.
Max.
in.
Max.
in.
Max.
in.
Max.
/0
AEIC
1.010
1.110
1.045
1.145
1.020
1.115
ICEA
1.010
1.110
1.055
1.155
1.045
1.145
1.020
1.120
2/0
AEIC
1.090
1.190
1.060
1.155
ICEA
1.105
1.200
1.090
1.190
1.060
1.160
3/0
AEIC
1.140
1.240
1.105
1.205
ICEA
1.155
1.255
1.140
1.240
1.105
1.205
/0
AEIC
1.195
1.295
1.160
1.255
ICEA
1.210
1.310
1.195
1.295
1.160
1.260
250
AEIC
ICEA
1.265
1.370
1.250
1.350
1.210
1.315
350
AEIC
1.355
1.470
1.310
1.420
ICEA
1.375
1.475
1.355
1.455
1.310
1.410
500
AEIC
1.480
1.600
1.430
1.540
ICEA
1.505
1.605
1.480
1.580
1.430
1.530
750
AEIC
1.670
1.795
1.610
1.725
ICEA
1.700
1.800
1.670
1.770
1.610
1.710
000
AEIC
1.815
1.945
1.760
1.875
ICEA
1.850
1.955
1.815
1.920
1.760
1.865
ICEA NOTE: Diameters specified in the above table are different than specified by AEIC CS8-00. Consult Accessory Manufac-
turer for proper selection of accessories. Diameters to be measured in accordance with 9.6.